Peter Kelly
 
Posts: n/a
Default Glow worm boiler problem

I have just fitted a new central heating circlation pump which is
located close to an old glow worm boiler.(lots of spanners, hammering)
The pump works fine but on starting the central heating after
completing the job the boiler would not work properly. The pilot light
kept going out. I bought a new themocouple thinking this was the
problem but still no joy. What happens is the pilot lights and stays
lit, when the main jets are fired up it works OK, but shortly after
there is a click and the main burner and pilot both cut out. Any
ideas?
  #2   Report Post  
 
Posts: n/a
Default Glow worm boiler problem



Peter Kelly wrote:
I have just fitted a new central heating circlation pump which is
located close to an old glow worm boiler.(lots of spanners, hammering)
The pump works fine but on starting the central heating after
completing the job the boiler would not work properly. The pilot light
kept going out. I bought a new themocouple thinking this was the
problem but still no joy. What happens is the pilot lights and stays
lit, when the main jets are fired up it works OK, but shortly after
there is a click and the main burner and pilot both cut out. Any
ideas?


Check the terminal assembly is clear, ours started going out after the
gas board *serviced* it, they vac out the boiler housing, but not the
flue/inlet duct, the thing just runs out of oxygen, and now being the
time of leaf fall it just might be....BTDT every 2 years!

Niel.

  #3   Report Post  
Bob Mannix
 
Posts: n/a
Default Glow worm boiler problem


"Peter Kelly" wrote in message
om...
I have just fitted a new central heating circlation pump which is
located close to an old glow worm boiler.(lots of spanners, hammering)
The pump works fine but on starting the central heating after
completing the job the boiler would not work properly. The pilot light
kept going out. I bought a new themocouple thinking this was the
problem but still no joy. What happens is the pilot lights and stays
lit, when the main jets are fired up it works OK, but shortly after
there is a click and the main burner and pilot both cut out. Any
ideas?


Nope, but I wouldn't mind some too. It may have nothing to do with the pump,
my Gloworm does this occasionally (but only when I'm not looking :-(). I
come home and it's off with no pilot light. My best guess at present is that
the pilot light jet is a bit blocked. I must get round to looking at it!


--
Bob Mannix
(anti-spam is as easy as 1-2-3 - not)


  #4   Report Post  
Christian McArdle
 
Posts: n/a
Default Glow worm boiler problem

The pump works fine but on starting the central heating after
completing the job the boiler would not work properly.


It sounds like some sort of cutout is operating. Are you sure that the pump
is working OK? In particular, did you reopen the isolating valves?

Christian.


  #5   Report Post  
Ed Sirett
 
Posts: n/a
Default Glow worm boiler problem

On Mon, 01 Dec 2003 10:23:31 +0000, Christian McArdle wrote:

The pump works fine but on starting the central heating after
completing the job the boiler would not work properly.


It sounds like some sort of cutout is operating. Are you sure that the pump
is working OK? In particular, did you reopen the isolating valves?

Are yes that one, along with failing to put the gas back on after purging,
pouring the contents of a removed waste trap down the nearest waste.
forgetting to switch on the plug before pushing back an appliance into its
hole...

Its some sort of circulation failure, could even be a dry pump. You did
bleed the pump by removing the end cap...

--
Ed Sirett - Property maintainer and registered gas fitter.
The FAQ for uk.diy is at www.diyfaq.org.uk
Gas fitting FAQ http://www.makewrite.demon.co.uk/GasFitting.html
Sealed CH FAQ http://www.makewrite.demon.co.uk/SealedCH.html




  #6   Report Post  
Peter Kelly
 
Posts: n/a
Default Glow worm boiler problem

Got close to solving the problem. Dissembled the pilot,igniter and
thermocouple assembly then undid the pilot jet from the pipe. At the
top of the pipe was a plug of carbon, removed this and the pilot light
was much larger, thus heating the thermocouple. Thought I had the
problem cracked but after 24 hours went out again may need to revisit,
will advise outcome.




"Christian McArdle" wrote in message .net...
The pump works fine but on starting the central heating after
completing the job the boiler would not work properly.


It sounds like some sort of cutout is operating. Are you sure that the pump
is working OK? In particular, did you reopen the isolating valves?

Christian.

  #7   Report Post  
Harry Bloomfield
 
Posts: n/a
Default Glow worm boiler problem

On 30/11/2003 "Peter Kelly" opined:-
I have just fitted a new central heating circlation pump which is
located close to an old glow worm boiler.(lots of spanners, hammering)
The pump works fine but on starting the central heating after
completing the job the boiler would not work properly. The pilot light
kept going out. I bought a new themocouple thinking this was the
problem but still no joy. What happens is the pilot lights and stays
lit, when the main jets are fired up it works OK, but shortly after
there is a click and the main burner and pilot both cut out. Any
ideas?


It sounds like either the thermocouple may need a bit of tightening
into its socket, or that the tip is not 'seeing' enough heat on its tip
when the main jets fire. Try moving the tip so it is better located in
the pilot flame and/or truning the pilot jet up a little if it is
adjustable.

--
Regards,
Harry (M1BYT)...

Remove the 'NOSPAM' in my email address to reply.

Free Amateur Radio Courses:-
http://www.ukradioamateur.org

Reply
Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules

Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Old Baxi WM 531 RS boiler problem David Hearn UK diy 8 December 1st 03 06:58 PM
Hot water problem with my combi boiler Andrew Bainbridge UK diy 1 October 25th 03 10:21 PM
Boiler Problem Gradually Getting Worse Frank Davis UK diy 1 October 23rd 03 10:00 PM
Boiler problem - hot water, cold radiators Dan the man UK diy 9 October 7th 03 11:26 PM
Is a Glow Worm 18HXI boiler any good? Tim Mitchell UK diy 5 July 31st 03 10:09 PM


All times are GMT +1. The time now is 02:54 AM.

Powered by vBulletin® Copyright ©2000 - 2025, Jelsoft Enterprises Ltd.
Copyright ©2004-2025 DIYbanter.
The comments are property of their posters.
 

About Us

"It's about DIY & home improvement"