On Sat, 25 Jun 2005 09:19:06 -0700, heinzy wrote:
Hi
After removing a radiator and capping the ends, I have a prob on my
combi Glow worm 80e boiler.
The boiler sounds like its starting when you open a tap, but then after
about 10secs, the lockout light comes on.
I drained the CH system before I removed the rad and afterwards,I bled
all the rads and refilled the system thru the filling loop.The pressure
is 2.5 on the boiler.
Surely , this is an air/pressure issue? , but I cant find any answers.
Many thanks to anyone who can help
See the Sealed CH FAQ.
Most likely the auto air vent in the boiler is closed or defective.
If you get that to work then the pressure may come down to something more
reasonable.
--
Ed Sirett - Property maintainer and registered gas fitter.