In an earlier contribution to this discussion,
Peter wrote:
I'm being dim, but I can't see the point of balancing radiators that
are fitted with TRVs?
Sure, you can run the whole system flat out with the TRVs open, but
surely as soon as they cut in the system will go out of balance and
undo all ones hard work?
If you *don't* balance such a system, the rads with the highest flow rate
will heat up first - and only when their TRVs close will the other rads see
any heat. Is this what you want?
--
Cheers,
Set Square